Abstract

This study examines the insulation resistance of underground conductors connecting 3-phase induction motors that drive pump machines. The results of the insulation resistance measurements were analyzed using the Polarization Index (PI) method and the Dielectric Absorption Ratio (DAR) method. There are 3 areas of conductor cables analyzed to calculate the remaining life of each conductor cable. For area 1, the remaining life of the inter-phase conductor cable is R-S 20.9 years, S-T 20.5 years T-R 20.8 years. Area 2, the remaining life of the inter-phase conductor cable is R-S 20.6 years, S-T 20.7 years T-R 21.1 years. For area 3, the remaining life of the inter-phase conductor cable is R-S 16.5 years, S-T 14 years T-R 15 years.

References

T. N. Bandung and I. Resistance, “Analisis Kondisi Isolasi Generator Unit 2 PT Indonesia XYZ Menggunakan Metode Pengujian Insulation Resistance dan Polarity Index,” pp. 1–13, 2024.

M. H. Indra, Yanolanda Suzantry Handayani, and I. Priyadi, “Pengujian Tahanan Isolasi Pada Transformator Distribusi 160 kVA Di PT. PLN (PERSERO) UP3 Bengkulu,” J. Amplif. J. Ilm. Bid. Tek. Elektro Dan Komput., vol. 12, no. 2, pp. 8–15, 2022, doi: 10.33369/jamplifier.v12i2.25274.

S. Aiyub, “Modul Beban Buatan Untuk Praktikum Distribusi Daya Listrk Di Laboratorium Distribusi Dan Proteksi Jurusan Teknik Elektro Politeknik Negeri Lhokseumawe A-205 A-206,” vol. 8, no. 1, pp. 205–209, 2025.

G. D. Prenata et al., “TEMPERATURE CLASSIFICATION IN HIGH VOLTAGE ELECTRICAL EQUIPMENT USING K-NEAREST NEIGHBOR KLASIFIKASI SUHU PADA PERALATAN LISTRIK TEGANGAN TINGGI MENGGUNAKAN K-NEAREST NEIGHBOR buatan dalam klasifikasi keandalan sistem tenaga listrik dapat memberikan hasil,” vol. 27, no. 1, pp. 40–49, 2025.

G. D. Prenata, “Klasifikasi Keandalan Sistim Distribusi Tenaga Listrik Di Pt. Pln (Persero) Up3 Surabaya Selatan Menggunakan Support Vector Machine (Svm),” J. Tek. Elektro, vol. 16, no. 2, pp. 62–70, 2023, doi: 10.9744/jte.16.2.62-70.

IEEE, “IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery IEEE Power and Energy Society,” Inst. Electr. Electron. Eng. Inc, vol. 43, pp. 9–14, 2000.

Published

2026-05-02